Good Flashings For Solar; Holes In Your Roof Made Waterproof

solar array on roof with wiring

Image credit: Solar Depot

There are many ways to make a weatherproof cable entry to your iron roof, but as far as I’m concerned, all of them except one are wrong. In this post, I’ll explain what 20 years of roofing experience has taught me about making the perfect wiring penetration.

It’s quite simple once you’ve seen the pictures, but as I explained last week, some builders have never been properly schooled on the finer points of waterproofing.

Mechanically Waterproof Is The Key

Building trades always joke that plumbers only need to know two things:

  1. Shit flows downhill
  2. Payday’s Thursday.

You’d think electricians would also be across these facts, but sadly, I’ve seen much evidence to the contrary. Not only do they rely heavily on great gobs of silicone sealant, but they are too precious to put their fingers into the sticky stuff and finish it nicely. And the failure to understand condensation inside conduits and wiring enclosures warrants a whole post of its own.

The golden rule is this;

Make your holes in the high part of the roofing sheet,

so the low part can carry the water without leaking.

Examining Flat Roof Failures

Failure #1

badly fitted wiring through roof

Stuck flat in the pan (the low part of a deck profile) with no less than nine screws.

  1. The red arrow shows the EPDM flashing torn through the reinforcing lip and ready to split further because it’s been hacked open with some side cutters instead of being cut accurately with sharp scissors.
  2. Covering screw heads to prevent corrosion and insure against leaks is good practice, but failing to remove the barcode means you’re relying on the integrity of a sticky label for sealing.
  3. The green arrow shows where silicone has been squirted around with a caulking nozzle but not worked into the gaps, finished or feathered at the edges.

You’d be surprised at the number of big, tough tradies who don’t like the feel of sealant on their fingers. Ewww!

People don’t realise that many sealants won’t adhere properly to the surface without expelling air and forcing it to make good contact.

Failure #2

badly executed roof holes

This is a damming indictment on solar installers, pun intended. By blocking the pan, water is stuck with nothing better to do than seep under the sealant & rust the roof.

High Ground Makes Things Happy

Klip Lok, high span, deep rib, and standing seam all describe roofing iron designed for low-pitch roofs. They all have flat sections – or pans – between the ribs.

wiring exiting from a roof

Just under the edge of the ridge cap, these two conduits emerge from the ribs of a roof sheet. The conduits and screws are up and away from the flat pans.

Klip Lok Should Look Like This

Seal the conduit to the sheet, add some for the flashing to slide over and secure it with screws that never get wet.

wiring emerging from a roof

Sometimes, you have to blow the water off, but urethane sealant will adhere to damp surfaces, whereas silicone won’t.

Some trades will argue that sawing holes through the rib weakens the sheet and makes it less able to carry foot traffic, so I put them near the roof purlins for support anyway. Ideally, it would help if you weren’t walking near flashings, in box gutters or where there are known weak points.

wiring exiting a roof

I only had 450mm headroom to work on these.

Corrugated Iron Shouldn’t Look Like This

There were/are small, oval-shaped flashings made for exactly this purpose, but most common these days are the 100mm square style, which sadly gets installed square to the profile with screws fired through it everywhere:

badly made roof wiring

Blue shading shows where water pools and dirt collects, while 6 out of 8 screws are in the wrong place.

Water pooling above these flashings is an unnecessary liability:

water pooling around wiring

Blue shading shows where water sits because the flashing prevents it from draining away.

 

Better Flashing Placement; Diamonds Are Forever

Remember the plumber’s mantra: shit flows downhill. By ensuring there’s nowhere for water to sit, you’ll minimise the chance of leaks, dirt buildup and corrosion.

correct way to make wiring leave a roof

Installing screws on the highest points means water can flow straight past them.

By filling the lower part of the corrugated profile, there’s no recess for the water to sit in and no way it can seep under the edge of the flashing.

I have formed a continuous downward slope with urethane sealant, working it into the surface with little circular finger motions to make it stick. Screws get covered next.

correct way to flash a hole in the roof

Water and the dirt it’s carrying are unimpeded here.

My Own House Looks Like This

Start with a measured amount of urethane sealant on a flashing already formed to fit the corrugations:

preparing an electrical conduit to go through a roof

Sealant makes a good lubricant on the conduit until it sets.

 

Set it in place with a saddle to hold the conduit while the sealant goes off. Using rigid conduit meant this was bent first, marked and trial fitted before breaking out the caulking gun full of mess:

rigid conduit exiting a roof

When everything fits nicely, you don’t need screws in to keep it there.

 

Finally, add some more sealant to fill the low spots. Feather the edges out to finish it off and create continuous fall. Yes, this conduit is going uphill.

finished wiring conduit going through roof

 

wiring conduit leaving a roof

From our cover image, this bushfire-rated job required plastic-coated metal conduit (anaconda) and gaps of no more than 1mm anywhere.

You’re Welcome To Share

After 20 years on the roof and no instruction from TAFE on the subject, I genuinely hope this helps make better installations.

Show this to anyone you know is dull enough to find it interesting, and if they have an argument against it, please leave a comment; I promise it’ll be ignored in due course.

Next week, we’ll touch on tile roofs and how not to wreck them with wiring.

About Anthony Bennett

Anthony joined the SolarQuotes team in 2022. He’s a licensed electrician, builder, roofer and solar installer who for 14 years did jobs all over SA - residential, commercial, on-grid and off-grid. A true enthusiast with a skillset the typical solar installer might not have, his blogs are typically deep dives that draw on his decades of experience in the industry to educate and entertain. Read Anthony's full bio.

Comments

  1. Alan Gregory says

    All of this is obvious and common sense- now that you have pointed it out clearly.
    I don’t fancy your chances of ever getting a plumber!

  2. Dave Ritson says

    Geez I hate Dektite’s with a passion!
    I have never seen one done neatly at all.

    Why not use a proper gland? They have a sealing gasket to start with.

    Use a 90° flexible conduit one, mount it on the flat area of ridge cap, face the end down hill. Done.
    https://www.idealelectrical.com/aie/category/Cable-Management/Protective-Hose-Accessories/Cable-gland/CORRUGATED-CONDUIT-PVC-ANGLED-GLAND-WITH-HOSE-LOCKNUT-32MM/CLI279AC32GY/p/10080250

    Or for tiles, use a masonry hole saw and fit one of these –
    https://cobaltsolar.com.au/roof-entries/

    https://www.idealelectrical.com/aie/category/Wiring-Accessories/Cable-Connector/Cable-entry-sleeve/DEDICATED-25MM-CORRUGATED-CONDUIT-ROOF-TILE-GLAND-ENTRY/COBCSE-REG-25/p/14277393

    These could also be used in the pans of Trimdek etc too.

    Anything is better than Dektite’s. Just because the “Standards” suggest a particular product as an example doesn’t mean it’s the best way to go about it. And shouldn’t prevent any other suitable product from being used.

    • Great point Dave! Thanks for sharing. Yes, why haven’t you mentioned these glands, Anthony? Seems like an excellent range of products to me. Dektites (not Dektite’s) massively increase the contact area with the roof, hence only creating the need for squeezing on no-more-skills. To me Dektites look like the last resort if nothing else works, and should be a rare exception not the standard.

    • Anthony Bennett says

      Good point about the Cobalt gland Dave,

      They’re a really nice solution I’ll give you that, and I have photos for another article in fact.

      Those plastic elbows are junk though 😉

      Cheers

  3. Thanks for the pointers, a few tips there I’ll be using next time to make it easier.

    One thing though – sealants are a lot healthier for your skin and less messy if you use disposable latex or nitrile gloves and a small spatula with soapy water, instead of your finger and spit

  4. Richard Courtenay says

    I don’t like holes in roofs at all, they are an abomination. My panels are raised 180mm off the roof with the supports running vertically not horizontally token them cool and stop the build up of leaves which when rotting produce a corrosive acid which will damage metal roofing. My cable runs in corrugated conduit from the combiner box, over the gutter and into the suffuit and sealed at both ends and shrouded from the heat. It has been like that for 16 years so far with no problems. So people like to hide everything but it has its disadvantages.

  5. You are definitely the exception, I’ll eat my boots if I come across a sparkie on site who can install a dektite.

    For stuff like corrie (and sometimes klip lok) I use a pan flashing that runs to the apex, cannot go wrong fixing to a flat surface.

  6. Thank you for the photos showing bending of rigid conduit is an art form still alive and well. I mastered conduit bending springs many moon ago. I hate the reliance these days on corrugated conduit, a product that is much weaker than the same diameter HD or UG conduit.

    Time will tell how thin corro conduit stands up to full sun exposure on north-facing roofs.

    Clive.

Speak Your Mind

Please keep the SolarQuotes blog constructive and useful with these 5 rules:

1. Real names are preferred - you should be happy to put your name to your comments.
2. Put down your weapons.
3. Assume positive intention.
4. If you are in the solar industry - try to get to the truth, not the sale.
5. Please stay on topic.

This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.

Get the latest solar, battery and EV charger news straight to your inbox every Tuesday